beautypg.com

C. electrical, D. startup, E. control function – Watts PWR2511 User Manual

Page 4

background image

4

C. Electrical

Note: It is the responsibility of the end user to ensure that the

installation is done according to local codes and regulations.
1. Make sure the on / off switch is in the off position (Figure # 1

item A).

2. Plug the unit into a standard 120 volt 3 prong outlet. An outlet

protected with a ground fault interrupt (GFI) is recommended.

D. Startup

1. Verify that the pretreatment equipment is installed and working

properly. Verify that no free chlorine is present in the feed water.

2. Verify that the on / off switch is in the off position.
3. Install a 10" five micron filter cartridge in the prefilter housing.
4. Open the reject control valve completely (Figure # 1 item C) by

turning it counterclockwise.

5. Close the reject recycle control valve (Figure # 1 item D) com-

pletely by turning it clockwise.

6. Open the feed water shutoff valve installed in step III-B-1 above.
7. Move the controller on/off switch to the on position.
8. Allow the unit to run for 15 – 30 minutes to flush the preservative

from the membrane(s).

9. Adjust the reject control valves (Figure # 1 items C & D) until the

desired flows are achieved. Closing the reject valve increases

the product flow and decreases the reject flow. Opening the

reject recycle valve decreases both the reject and product flow.

See the flow rate guidelines and temperature correction table in

the appendix to determine the flow rates for different operating

temperatures. Do not exceed 200psi on the pump discharge

gauge (Figure #1 item F).

10. Allow the product water to flow to drain for 30 minutes.
11. Turn off the system and connect the product line to the point of

use. The product water line should never be restricted. Mem-

brane and/or system damage may occur if the product line is

blocked.

12. Restart the system and record the initial operating data using the

log sheet.

E. Control Function

1. When the on / off switch is in the on position, the inlet valve

opens and the pump runs. If the product pressure switch is used

then the pump will cycle based on the product water pressure.

The switch is factory set to cut off at 40psi and cut on at 20psi.

Instructions for adjusting the cut off and cut on pressures are

located on the inside cover of the switch.

2. If the water pressure feeding the pump drops below 5psi for more

than 5 seconds, the pump will turn off and the amber light on the

control box will turn on. The controller will automatically reset after

30 minutes and the pump will turn back on. Cycle the on / off

switch to manually reset a low-pressure shutdown.

3. Autoflush – This is a feature that provides increased reject flow

at startup and for 2 minutes every hour. The timer is prepro-

grammed at the factory and should not be adjusted.

Figure 1

G

M

L

Figure 1