Automatic control valve data, Bic 1000 specification drawing, Acv only typical performance data – Watts BIC-1000 User Manual
Page 3

3
H
Height from
Flange To Top
Automatic Control Valve Data
BIC 1000 Specification Drawing
Configuration Data -
Typical BOM and Drawing
Valve Station Component Requirements
ITEM
QTY
DESCRIPTION
MATERIAL
SIZE
CONNECT
1
1
SHUT-OFF VALVE
Contact Factory
FLANGE
2
OPTIONAL
FLOW METER
Contact Factory
FLANGE
3
1
FLANGE X THREAD ADAPTOR
304 SS / ZN PLATE STEEL
FLANGE
4
1
DIAPHRAGM ACTUATED CONTROL VALVE
FBE / DI / SST
FLANGE
5
1
FLANGE X GROOVE ADAPTOR
304 SST
FLG X GRV
6
1
GROOVE COUPLER
EPOXY COATED DI
GROOVE
7
1
RELIEF VALVE
BRASS / BRONZE
FLANGE
8
1
OUTLET HEADER
304 SST
FLANGE
9
1
SHUT-OFF VALVE
Contact Factory
FLANGE
10
3
SPACER FLANGE - SLOTTED - NOT SHOWN
304 SST
FLANGE
NOTE: See specific component specifications or literature for detailed component material descriptions
FLOW RATE CAPACITIES - GPM
PRESSURES - PSI
LINE SIZE
CONTINUOUS
INTERMITTENT*
MINIMUM
MAX INLET
MIN DP
SET POINT RANGE
2
210
260
1
170
20
40 - 120
3
460
570
30
170
20
40 - 120
4
800
1000
50
170
20
40 - 120
6
1800
2300
115
170
20
40 - 120
*Based on:
a - Max capacity through the ACV for a system with a 20psi or greater pressure reduction requirement
FLOW RATES - GPM
FALL OFF FROM SET POINT @ - PSI
LINE SIZE
20% CONT
20% INTERMIT
20% CONT
20% INTERMIT
100% CONT
100% INTERMIT
2
42
52
0
1
4
6
3
92
114
0
0
1
2
4
160
200
0
1
2
4
6
360
460
0
0
1
2
X
Hydro test the fully assembled Valve Station to 175psi for 5 minutes without leakage.
JOB NAME
CUSTOMER
ENGINEER
RFQ#
ACV ONLY
Typical Performance Data
CC - Center Line of Inlet / Outlet Pipes
1
2
3
4
5
6
7
8
9
Typical Configuration Drawing - Above Ground Installation