beautypg.com

Specifications – Banner Q45 Series User Manual

Page 7

background image

Specifications

Supply Voltage and Current

90 to 250 V ac (50/60 Hz)
Average current 20 mA
Peak current 500 mA at 120 V ac, 750 mA at 250 V ac

Supply Protection Circuitry

Protected against transient voltages

Output Configuration

SPDT (Single-Pole Double-Throw) electromechanical

relay output. All models except emitters.

Output Rating

Max. switching power (resistive load): 150 W, 600 VA
Max. switching voltage (resistive load): 250 V ac, 30

V dc
Max. switching current (resistive load): 5 A at 250 V

ac
Min. voltage and current: 5 V dc, 0.1 mA
Mechanical life of relay: 10,000,000 operations
Electrical life of relay at full resistive load: 100,000

operations

Output Protection Circuitry

Protected against false pulse on power-up

Output Response Time

15 milliseconds ON and OFF
(NOTE: 100 millisecond delay on power-up. Output is

de-energized during this time.)

Environmental Rating

NEMA 6P, IEC IP67

Operating Conditions

Temperature: –40 °C to 70 °C (–40 °F to 158 °F)
Maximum relative humidity: 90% at 50 °C (non-

condensing)

Certifications

Repeatability

Opposed mode: 0.25 milliseconds
All other sensing modes: 0.5 milliseconds
Response time and repeatability specifications are

independent of signal strength.

Adjustments

Light/Dark Operate select switch and multi-turn

Sensitivity control (allows precise sensitivity setting –

turn clockwise to increase gain).
Optional logic and logic/display modules have

adjustable timing functions.

Indicators

Indicator LEDs are clearly visible beneath a raised

transparent Lexan

®

dome on top of the sensor

Power (green) LED lights when 90 to 250 V ac power

is applied
Signal (red) AID

System LED lights when the sensor

sees its modulated light source and pulses at a rate

proportional to the strength of the received light

signal
Load (amber) LED lights whenever the output relay is

energized
Optional 7-element LED signal strength display

modules

Construction

Molded reinforced thermoplastic polyester housing, o-

ring-sealed transparent polycarbonate cover, molded

acrylic lenses, and stainless steel hardware. Q45s are

designed to withstand 1200 psi washdown.
The base of cabled models has a 1/2-inch NPS integral

internal conduit thread.

Connections

PVC-jacketed 2-wire (emitters) or 5-wire (all others) 2

m (6.5 ft) or 9 m (30 ft) unterminated cables, or 3-

pin (emitters) or 5-pin (all others) Mini-style quick-

disconnect (QD) fittings are available (“Q” - suffix

models).
QD cables are ordered separately.

Application Notes

Transient suppression is recommended for contacts

switching inductive loads.
Optional output timing modules are available.

Q45VR2 Series Sensors

P/N 36339 Rev. F

www.bannerengineering.com - tel: 763-544-3164

7