Maxi-amp cl series, Timing logic programming, Hookup of multiple self-contained sensors – Banner MAXI-AMP Series User Manual
Page 4: Cl5 models)

(NOTE: see page 5 for
description of logic functions)
The diagram shows switch locations,
and the table summarizes the program
switch positions.
A group of ten switches located on one side of the module is used to select the timing logic
for CL5 models.
Switches #1 through #7 are used to select the logic function. Switch #8 programs the output
for either NORMALLY OPEN or NORMALLY CLOSED operation. Switches #9 and #10
program the time range(s). There are three ranges: 10 to 150 milliseconds, 0.1 to 1.5 seconds,
and 1 to 15 seconds. The programmed range will be the same for
both functions of a dual
timing mode (ON & OFF DELAY, DELAYED ONE-SHOT, and REPEAT CYCLE). However,
DELAY and HOLD times are independently adjustable within the selected range.
4
LIGHT OPERATE
DARK OPERATE
DARK OPERATE
If any receiver "sees"
light
When all receivers
"see" dark
OUTPUT OCCURS
(AFTER DELAY, IF
ANY)
If any receiver "sees"
dark
When all receivers
"see" light
NO
NO
YES
YES
LIGHT OPERATE
INVERTING JUMPER
Installed Between Module
Terminals #10 and #11
SENSOR PROGRAM:
Light or Dark Operate
LOGIC DESCRIPTION
Hookup of Multiple Self-contained Sensors
Any number of self-contained dc sensors may be wired together
in parallel to a single CL Series MAXI-AMP module to create
almost any multiple-sensor logic configuration. Power for the
sensors may be obtained from MAXI-AMP 400mA power
supply CP12 (shown below) or from 1-amp model PS120-15.
The table at the right describes how the four most frequently
used multiple-sensor logic configurations may be created.
MINI-BEAM SM312 Series and VALU-BEAM SM912 Series
sensors have a switch on the back of their housings which is
used to program the sensors for LIGHT or DARK operate.
MAXI-BEAM sensors are set for LIGHT or DARK operate
using the programming ring. MULTI-BEAM sensors are
programmed for LIGHT or DARK operate with the logic
module jumper wire. OMNI-BEAMs are programmed by a
switch in the sensor block.
For ON/OFF sensor operation,
light operate is equated to
normally open output, and dark operate is defined as normally
closed. EZ-BEAM sensors have both a normally open and a
normally closed output. Selection of either output determines
the LIGHT/DARK operate mode. ECONO-BEAM sen-
sors are not programmable and must be ordered for LIGHT
OPERATE (standard models) or DARK OPERATE (model
suffix "NC").
The addition of a jumper wire between MAXI-AMP terminals
#10 and #11 changes the input response from a low-going to a
high-going signal. This feature, combined with the selection
of LIGHT or DARK operate at the sensor, allows "AND" logic
with parallel sensor connections.
LIGHT "OR"
DARK "AND"
DARK "OR"
LIGHT "AND"
Timing Logic Programming
(CL5 models)
Settings illustrated below are factory settings. Factory settings are "underlined" in the table.
MAXI-AMP CL Series
Brown�
+V dc
Brown�
+V dc
Blue�
(#1)
White
+V dc
Brown
105-130V
AC �
Blue�
(#1)
SM31R/RL
White
SM31R/RL
SM31E/EL Blue�
(#1)
Brown�
+V dc
Blue
SM31R/RL
White
CL3�
or �
CL5�
model
8
7
6
5
4
9
10
11
1
2
3
CP12�
power
supply
8
7
6
5
4
9
10
11
1
2
3
SM31E/EL Blue�
(#1)
Brown�
+V dc
SM31E/EL Blue�
(#1)
Brown�
+V dc
105-130V ac