Teaching limits using two-point static teach – Banner T-GAGE M18T Series Temperature Sensors User Manual
Page 4

Teaching Limits Using Two-Point Static TEACH
Two-Point TEACH is the traditional setup method, used when two conditions can be presented individually by the user. The sensor es-
tablishes a single sensing threshold (the switchpoint) midway between the two taught conditions, with the Output ON condition on one
side and the Output OFF condition on the other.
General Notes on Programming
• The sensor will return to RUN mode if the first TEACH condition is not registered within 60 seconds
• After the first limit is taught, the sensor will remain in PROGRAM mode until the TEACH sequence is finished
Switching
Hysteresis
OFF
Threshold
Cold
Limit
Hot
Limit
0° C
300° C
2nd taught
(Output OFF)
Condition
1st taught
(Output ON)
Condition
ON Threshold
(Set at midpoint of
taught conditions)
When object to be sensed is hotter than ambient
Switching
Hysteresis
OFF
Threshold
Cold
Limit
Hot
Limit
0° C
300° C
1st Taught
(Output ON)
Condition
2nd Taught
(Output OFF)
Condition
ON Threshold
(Set at midpoint of
taught conditions)
When object to be sensed is colder than ambient
Figure 3. Two-Point Static Teach
Two-Point TEACH Procedure
Result
Push Button
Remote Line
(0.04 sec < T < 0.8 sec)
Programming
Mode
• Push and hold
push button for 2
seconds
No action required
• Power LED turns Red
• Output LED turns Yellow
Learn Output
ON Condition
• Present Output ON
condition
• "Click" the push
button
• Present Output ON condition
• Single-pulse the remote line
T
• Output LED turns OFF
Learn Output
OFF Condition
• Present Output
OFF condition
• "Click" the push
button
• Present Output OFF condition
• Single-pulse the remote line
T
Teach Accepted
• Power LED turns Green
• Sensor automatically sets the switch-
ing threshold and returns to Run
mode
Teach Unacceptable
Sensor returns to beginning of Teach
Exit Without
Save
• Push and hold
push button for 2
seconds
• Hold remote line low for 2 sec-
onds
2 seconds
Sensor returns to Run mode without sav-
ing new settings
M18T T-Gage Sensor
4
www.bannerengineering.com - tel: 763-544-3164
P/N 120632 Rev. A