Disconnect network, Start network – Rockwell Automation T3831 ICS Regent Communications Package for Winterpret User Manual
Page 23

Communications Package for
W
INTERPRET
(T3831)
P D - 6 0 4 1 M a r c h , 0 6
23
Table 6. Commands Not Allowed While Network is Active.
Load Program
Run Program
Stop Program
Scan Program
Delete Program
Reset Local Variables
Load RAMcode
Load I/O Configuration
Load Shared Variable Allocation
Start/Stop Inputs/Outputs
Load Network
Unload Network
Voted Reset (command disallowed — use reset
buttons on processor modules)
Compare to Regent (I/O Configuration)
In order to perform any of these functions from W
INTERPRET
,
you should use the Disconnect Network command to
deactivate the GPL communications for the necessary Regent.
Disconnect Network
The Disconnect Network command deactivates the primary
functions for GPL communications. After disconnecting the
Regent, the input variables are set to their final values (if so
configured). While the Regent is disconnected, it does not
respond to any poll requests from a Net Master and does not
process any input data broadcasted by other Regents on the
GPL network.
Use the Disconnect Network command to deactivate the
network if you need to perform any of the commands listed in
Table 6. After performing the necessary commands use the
Connect Network command to activate the network.
Start Network
The Start Network command activates the Net Master
function for a Regent that is configured with a Net Master
port. If the Regent does not have a Net Master port, this
command has no effect.