Rockwell Automation DeviceNet KwikLink Configuration Drawing with Notes User Manual
Devicenet kwiklink lite popular configuration, Parts catalog table
DeviceNet KwikLink Lite Popular Configuration
Note: Performance is what we tested,
not the max capacity
1
2
3
4
2
1
3
4
B
B
A
A
Red
24 VDC
White
CAN_H
Blue
CAN_L
Black
0V DC
V+
V-
Valve Bank
1799-ZC10V
Stack Lights
Stack Lights
Series 9000
Sensor
ArmorBlock I/O
ArmorStart
871TM
Proximity
Sensor
Limit
Switch
EM
ERGENC
Y
20’
RightSight
Photoelectric
Sensor
CompactBlock I/O
Parts Catalog Table
Connectors RA Part number Description
1485P-K1GK4
Flat cable to Thin Round Cable
Converter, IDC
1485P-K1TLR4
Power Tap
1485P-K1TG4
Trunk-line Connector IDC
1485P-K1DL4
Drop-line Connector IDC
1485P-K1TR4
Terminating Resistor IDC
1485A-KCrimp
Crimping Pliers
1485P-K1G4-Y5
5-pin Open Style Connector IDC
Media
RA Part number Description
1485C-P1W100
IP20 Flat Media Cable Spool, 100 meters
1485C-P1W300
IP20 Flat Media Cable Spool, 300 meters
1485C-P1W600
IP20 Flat Media Cable Spool, 600 meters
LINK 1
LINK 2
MOD
NET
0
2
1
13
14
4
3
11
12
6
5
P
W
R
9
7
8
0
2
4
6
8
X10
X1
X100
10
15
0
2
4
6
8
0
2
4
6
8
1732 ArmorBlock I/O
• Digital 24V DC I/O
• 8 or 16 points per block with 1 block
per node for greater module density
• Mounts anywere on machine, resulting
in shorter cable runs
871TM Inductive Proximity Sensor
• 10-30V DC or 40-250V AC/DC
• NEMA 4X, IP67 all models
• 1200psi washdown
• Available sensing: Standard,
Extended/Equal, FERROUS only,
Non FERROUS only
PowerTap has Built-in
Terminating Resistor
Wire Way
KwikLink Lite Media is rated for Class 2 operation and
all applicable NEC codes should be adhered to during its
installation. The cabling system is rated IP20 and it
should be installed inside an enclosure or in a dry and
oil free environment. Use of a wire tray is recommended.
RightSight
RightSight DeviceNet Senors:
• Strobing and COS protocols
• ON delay, OFF delay and one shot timers
• Adjustable counter with output
• Adjustable motion detection
• Dual margin threshold diagnostics
• Autobaud
Stack Lights
• Control Tower™ stack lights provide
multi-status indiction of your application
• Available in three sizes: 30mm, 50mm,
and 70mm with UL Type 4/4X/13/IP65
ratings
Powered
Roller
Controller
START
STOP
1799
• The 1799D has universal inputs
• DeviceLogix allows local logic execution that enables the fast
speed required for high performance conveying
• Configuration is done through RSNetWorx for DeviceNet
KwikLink Lite
Terminator
DeviceNet KwikLink Lite Media Guidelines
KwikLink Lite
Cable Color Code
Data Rates
125k baud
250k baud
500k baud
KwikLink Lite Trunk Distance 350m
150m
55m
Number of Nodes
64
Max. Drop Length
6.1m
Cumulative Drop
159m
78m
39m
193-DNCT
DeviceNet
Configuration
Terminal
7
A
ESC
B
SEL
C
RESET
D
E
8
9
F1
F2
F3
F4
4
5
6
1
2
3
F
Copy
Exp
.
Help
0
SHIFT
Paste
+/-
24 Vdc Class 2
Assembly
Power Supply
Allen-Bradley
To plantwide network
infrastructure
193-EE
Electronic Overload
CompactLogix with
1769-SDN/B DeviceNet scanner
Publication IASIMP-QR021A-EN-P—May, 2010
IASIMP-QR021A-EN-P:Layout 1 5/26/10 3:06 PM Page 1