Rockwell Automation FlexPak Plus M-Contactor Adapter Kit 14C470 User Manual
Accessory mćcontactor adapter kit
INSTRUCTION MANUAL DĆ3955
ACCESSORY
MĆCONTACTOR ADAPTER KIT
MODEL NUMBER 14C470
ASSEMBLY DRAWINGS 705388
The equipment described below should be installed only by qualified electrical maintenance personnel
familiar with the construction and operation of the equipment and the hazards involved.
DESCRIPTION
The Contactor Adapter Kit provides a means of conĆ
necting the optional userĆsuppliedM contactor (and
optional userĆsuppliedreversing M contactor) to the
optional Basic FlexPak Plus Controller 14C320 thru
14C325 which is suppliedwithout the auxiliary panel.
The Kit is an assembly consisting of an Auxiliary MountĆ
ing Bracket, a power terminal strip, two wire harnesses
andfour screws anda pilot relay.
INSTALLATION
WARNING
BEFORE ATTEMPTING TO INSTALL THIS FLEXĆ
PAK PLUS MODIFICATION KIT, DISCONNECT
AND LOCK OUT ALL SOURCES OF INCOMING
POWER TO THE CONTROLLER.
1. Orient the Auxiliary Mounting Bracket (Refer to FigĆ
ure 1) over the Basic Controller aligning the mountĆ
ing holes. Secure the Bracket with the provided
washers andscrews. Make sure the washer teeth
are firmly embedded in the Chassis to provide
proper ground.
2. Connect user supplied115VAC, 3 amp max power
to 188Ć189 on pilot relay PC. Now connect the
orange lead(139) from the pilot relay harness to the
controller regulator printedcircuit card(refer to FigĆ
ure 1.)
3. Wire the optional userĆsuppliedM contactor (and
optional userĆsuppliedreversing contactor) to the
kit terminal strip according to Figure 2A or 2B. Also,
refer to Figures 5.8, 5.9, 5.11 and5.12 of DĆ3938 for
additional wiring diagram information.
PILOT
RELAY PC CARD
MĆCONTACTOR
ADAPTOR KIT
BASIC CONTROLLER
POWER MODULE
Figure 1 - MĆContactor Adapter Kit Mounted To Basic Controller