beautypg.com

Rockwell Automation T8160 Trusted TMR Interface User Manual

Sds-8160 trusted, Industrial control system trusted, Tmr interface-t8160

background image

SDS-8160
Trusted

TM

Industrial Control System

Trusted

TM

TMR Interface-T8160

Issue 5 Jan 2006

FRONT PANEL

DESCRIPTION


The

Trusted

TM

TMR

Interface

provides an interface between a
Trusted

TM

Controller and Regent,

Regent+Plus I/O systems. The
module supports the existing Regent
I/O Safetybus™, and the use of all
Regent

and

Regent+Plus

I/O

modules as part of an I/O sub-
system.

The module consists of three identical
processor sub-systems containing a
Bus Interface, an I/O processor with
its associated memory, and a power
supply.

Each processor sub-system has an
interface to the triplicated Inter-
Module Bus (IMB) and I/O Safetybus.
The I/O Processors interface with the
Safetybus, linking the field I/O
modules to the Trusted

TM

TMR

Processor.

The three processor sub-systems
operate in lock-step synchronization,
providing 2-oo-3 hardware voting on
every data exchange between the
Trusted

TM

TMR Processor and the

I/O sub-system. This ensures
uncompromised fault detection and
error-free operation.

The triplicated Power Supply Unit
receives dual redundant +24v dc
supplies

from

the

Trusted

TM

Controller backplane, and converts
the supply to the logic levels required
by the module circuits. The module is
capable of operating with a failure of
either of the redundant power feeds.

The module scans the I/O sub-system
and exchanges data with the
Trusted

TM

TMR Processor. Data

from inputs are read from the I/O
modules in the I/O sub-system.
Outputs are driven by transmitting
data through the I.O Processor to the
I/O module. Output Data from the
Trusted

TM

TMR Processor to the I/O

module is in the required format for
Regent+Plus.

Communications

between

the

Trusted

TM

TMR Processor and the

I/O Processor are maintained through
shared RAM used as a ‘mail box’ for
data transfers between the two.

FEATURES

Supports the use of all Regent
and Regent+Plus I/O modules

Triplicated interfaces to
Trusted

TM

TMR Processors and

Regent+Plus I/O sub-systems

Hot replaceable

Module fault and status
indicators

IEC 61508, SIL 3 safety
applications