Block diagram, Single channel schematic, Electrical specification – Rockwell Automation T8802 Trusted 60 Channel 24V dc Digital Input FTA User Manual
Page 2: Sds-8802 trusted, Industrial control system trusted
![background image](/manuals/581546/2/background.png)
SDS-8802
Trusted
TM
Industrial Control System
Trusted
TM
60 Channel 24V dc Digital Input FTA - T8802
ICS Triplex
Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-
www.icstriplex.com
BLOCK DIAGRAM
Single Channel Schematic
ELECTRICAL SPECIFICATION
Voltage Range (Field Supply)
18 to 28V dc
Fuses
61-off 50mA
Maximum Current (Field Supply)
3A
Recommended Operating Current
6.4mA per channel maximum
Power Consumption (Field Supply)
10W maximum
MECHANICAL
SPECIFICATION
Dimensions (HxWxD):
110mm x 455mm x 68mm
(4.3ins x 17.9ins x 2.6ins)
Weight (fully populated)
762gms
(1.68lbs)
ENVIRONMENTAL
Operating Temperature:
-5
°C to 60°C
(23
°F to 140°F)
Operating Humidity:
5 to 95%, non-
condensing
Vibration:
10 to 57Hz
±0.075mm
57 to 150Hz 1.0g
Shock:
15g, ½ sine wave, 11ms
EMI (IEC 801):
ESD
Air discharge to 15kV.
Contact discharge to 8kV
Radiated Fields
10V/m, 27MHz to
500MHz
Transients and Bursts
2kV, 2.5kHz for
t=60 seconds