beautypg.com

Fault mode jumper, Keying – Rockwell Automation T3444 ICS Regent 110 VAC Digital Output Module User Manual

Page 8

background image

AC Digital Output Module (T3444)


8

Industrial Control Services

Fault Mode Jumper

The fault mode jumper is located behind the ID switch cover
in the lower left-hand corner of each I/O chassis. The position
of the fault mode jumper determines the module's response to
system level faults. The fault mode jumper’s position will
cause all output modules in the I/O chassis to either shutdown
(turn off all outputs) or to hold (hold the last state) after a
system level failure occurs. An example of a system level
failure is the failure of two processor modules.

Keying

The I/O chassis can be physically keyed to prevent accidental
damage caused by inserting a module into a slot wired for a
different module type. Figure 5 illustrates how the slot keys
are installed on the I/O chassis slot field wiring connectors.
The slot key positions for the AC digital output module are
listed in Table 1.

Table 1. Slot Key Positions.

Module

Upper

Connector

Lower

Connector

T3444

15

10