3.3. Module – 8162 (Bridge Module)
DESCRIPTION
This definition provides module status for a 8162 primary chassis expansion interface module that
provides an expansion bridge from Trusted
TM
to CS300 systems.
The logical module accounts for the 3 physical modules FCR-A, FCR-B and FCR-C.
OEM PARAMETERS:
OEM parameter Valid numbers Description
CHASSIS
2-29
Logical chassis number allocated to the primary CS300 chassis in
which the 8162 modules are placed.
SLOT
16
Logical slot within the Primary CS300 chassis by which the Trusted
TM
system identifies the 8162 module. This cannot be configured.
PHYSICAL MODULE:
RACK 1: [STATUS] - 6 BOOL Inputs
Variable 1:
TRUE = Logical module responding
Variable 2:
TRUE = FCR-A faulted or not responding
Variable 3:
TRUE = FCR-B faulted or not responding
Variable 4:
TRUE = FCR-C faulted or not responding
RACK 2: [INFO] - 12 ANALOGUE Inputs
Word 1:
FCR-A fault code (see note 1)
Word 2:
FCR-B fault code (see note 1)
Word 3:
FCR-C fault code (see note 1)
Word 4:
FCR-A hot-link error count
Word 5:
FCR-B hot-link error count
Word 6:
FCR-C hot-link error count
Word 7:
FCR-A IML own-link error count
Word 8:
FCR-A IML down-link error count
Word 9:
FCR-A IML up-link error count
Word 10:
FCR-B IML own-link error count
Word 11:
FCR-B IML down-link error count
Word 12:
FCR-B IML up-link error count
Word 13:
FCR-C IML own-link error count
Word 14:
FCR-C IML down-link error count
Word 15:
FCR-C IML up-link error count
[Note 1 - Fault Codes]
0
: No fault
1
: Local backplane fault
2
: Local expansion bus fault
3