beautypg.com

Block diagram, Electrical specification, Sds-8290 trusted – Rockwell Automation T8290 Trusted Output Power Distribution Unit User Manual

Page 2: Industrial control system trusted, Output power distribution unit-t8290

background image

SDS-8290
Trusted

TM

Industrial Control System

Trusted

TM

Output Power Distribution Unit-T8290

ICS Triplex

Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-

www.icstriplex.com

BLOCK DIAGRAM

ELECTRICAL SPECIFICATION

Voltage Range

0 to 140V dc

Supply Current

60A max

Supply Connection +ve

2-off M6 x 25mm studs

0V Reference Connector (not 0V
return)

BLZ 2-part terminal

Power Output (3-off)

6-way AMP MATE-N-LOK connector

0V Reference Connector (3-off)

5-way BLZ 2-part terminal

Conductor Clamping Range

0.5 to 2.5mm

2

MECHANICAL
SPECIFICATION


Dimensions (HxWxD):
70mm x 90mm x 50mm
(2.75ins x 3.54ins x
1.97ins)

Weight (fully populated)
106gms
(0.23lbs)

ENVIRONMENTAL


Operating Temperature:

-5

°C to 60°C

(23

°F to 140°F)


Operating Humidity:
5 to 95%, non-
condensing

Vibration:
10 to 57Hz

±0.075mm

57 to 150Hz 1.0g

Shock:
15g, ½ sine wave, 11ms

EMI (IEC 801):
ESD
Air discharge to 15kV.
Contact discharge to 8kV

Radiated Fields
10V/m, 27MHz to
500MHz

Transients and Bursts
2kV, 2.5kHz for
t=60 seconds