Isolated Guarded Digital Output Module (T3485)


2 0

Industrial Control Services

quarter turn from its locked position releases the fuse holder,
extending the fuse and allowing it to be removed.

To prevent damage to the module, replacement fuses must be
of the same rating and type (see Specifications, below).

Safety Considerations

The Isolated Guarded output module is TÜV certified to Risk
Class 5 for safety critical outputs. The modules are approved

for de-energize to trip safety critical outputs in single or dual
module configurations.

The modules are also approved for energize to trip safety
critical outputs in dual module configuration only if the
outputs are dynamically transitioned at a period not greater
that six months (to verify the signal wiring and load device
integrity).

Specifications

Safetybus Power

1.75 load units

Number of Outputs

Eight, isolated

Voltage Range

12 to 130 VAC
15 to 150 VDC

Frequency Range (Vac)

47 to 63 Hz

Output Load Current (Iout)

(0 to 40

°

C)

derating (at 60

°

C)

2.0 amps max. (see page 10)

1.5 amps max. (see page 10)

Module Load Current (Imod)

for Iout < 1.5 amps

for Iout > 1.5 amps

12 amps (0 to 40° C),
derated linearly to 8 amps at
60° C

8 amps (0 to 40° C), derated
linearly to 6 amps at 60° C

On State Drop

2.5 volts, maximum