Multiplexed I/O Module (T3491)


P D - 6 0 3 5 M a r - 0 6

19

Operating Humidity

0 to 95% relative humidity,
non-condensing

Vibration

10 to 55 Hz:

±0.15mm

Shock

Operating:

15 g, ½ sine wave, 11 msec

Electromagnetic
Interference

IEC 801 Part 2 - Electrostatic

Discharges

IEC 801 Part 3 - Radiated

Electromagnetic Fields

IEC 801 Part 4 - Transients

and Bursts

ANSI/IEEE C37.90 - Surge

Withstand Capability


Level 3: Contact discharge of
6 kV
Level 3: 10 V/M, 27 MHz -
500 MHz
Level 4: 2 kV, 2.5 kHz for t =
60 seconds
2.5 kV damped 1 MHz sine
wave
4 kV bi-directional impulse,
10 nsec rise time, fast
transient

Safety

Certified to DIN V VDE
0801 for Risk Class 5, non-
interfering. Also designed to
meet UL 508 and CSA 22.2,
No. 142-M1981

Dimensions

Height:

Width:

Depth:


12.6" (320 mm)
1.27" (32 mm)
10.12" (257 mm)

Weight