Rockwell Automation MDO16FNS 16-Channel Digital Output Module 120Vac/dc User Manual
Page 3
MDO16FNS October 2005 – Issue 4
3
Triguard SC300E MDO16FNS 16-Channel D/O Module 120Vac/dc
SPECIFICATION
Model
MDO16FNS
Channels
16
Architecture
TMR
Indicators:
Input
Modules
One per point
Health, 3 x On Line
Output driver
FET
Voltage range
99 to 132Vac/dc
Voltage drop
Less than 4V
Maximum drive
Resistive load: 0.50A per channel
Tungsten load: 0.125A per channel
Surge limiting
3A peak
Isolation
1kVdc field to system, commoned supply
Module power consumption excluding field
power dissipation in module
12mA (24mA if dual slot hot repair)
4W
Module power consumption including field
power dissipation in module
2W @ minimum load
36W @ maximum load
Overall size (mm)
Overall size (inches)
400(9U)H x 397L x 28W
15.75H x 15.63L x 1.1W
Weight
2.1kg
ENVIRONMENTAL SPECIFICATIONS
The maximum ambient temperature measured at the hottest point within the Triguard system
shall not be greater than 60 degrees centigrade.
Temperature operating:
+5°C to +60°C
Temperature storage:
-25°C to +70°C
Humidity
5% to 95% non-condensing at ambient <40°C
EMC/RFI Immunity
Tested and certified to IEC 1131-Part 2 1994
Vibration/Shock
Tested and certified to IEC 1131-Part 2 1994
Certification:
General Certification: Ref. SC300E TMR Product Guide (ref 008-5209).