Rockwell Automation T3468A ICS Regent DC Guarded Digital Output Modules User Manual
Page 19

(T3461A, 62A, 68A) DC Guarded Digital Output Modules
P D - 6 0 1 9 M a r - 0 6
19
Isolation
2500 volts minimum (field
wiring to control logic)
2500 volts minimum (output
group 1-4 to output group
5-8)
Operating Temperature
0
°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-40
°
to 85
°
C
(-40
°
to 185
°
F)
Operating Humidity
0 to 95% relative humidity,
non-condensing
Vibration
10 to 55 Hz:
±0.15mm
Shock
Operating:
15 g, ½ sine wave, 11 msec
Electromagnetic
Interference
•
IEC 801 Part 2 - Electrostatic
Discharges
•
IEC 801 Part 3 - Radiated
Electromagnetic Fields
•
ANSI/IEEE C37.90 - Surge
Withstand Capability
Level 3: Contact discharge of
6 kV
Level 3: 10 V/M, 27 MHz -
500 MHz
2.5 kV damped 1 MHz sine
wave,
4 kV bi-directional impulse,
10 nsec rise time, fast
transient
Safety
Certified to DIN V VDE
0801 for Risk Class 5. Also
designed to meet UL 508 and
CSA 22.2, No. 142-M1981
Dimensions
Height:
Width:
Depth:
12.6" (320 mm)
1.27" (32 mm)
10.12" (257 mm)
Weight
3.5 lbs (1.6 kg)