Safety considerations, Specifications – Rockwell Automation T3488/T3488A ICS regent Monitored Guarded Output Modules User Manual
Page 23
Monitored Guarded Output Modules (T3481/81A, 84 and 88/88A)
P D - 6 0 3 3 M a r - 0 6 (Issue 2)
23
Safety Considerations
The Monitored Guarded output modules are TÜV certified to
Risk Class 5 for safety critical outputs. The modules are
approved for de-energize to trip safety critical outputs in
single or dual module configurations.
The modules are also approved for energize to trip safety
critical outputs in dual module configuration, but only if the
fault name variables are configured and used to automatically
alarm and annunciate the detection of load/fuse faults to plant
operations personnel.
Specifications
Safetybus Power
1.5 load units
Number of Outputs
16 circuits divided into two
groups of 8 circuits each
T3481 (81A)
T3484
T3488 (88A)
Voltage Range
18 to 36 VDC
90 to 130 VAC
95 to 140 VDC
Frequency
N/A
47 to 63 Hz
N/A
Load Current
(0 to 40
°
C)
derating
(at 60
°
C)
2 amp
1.5 amp
0.7 amp
0.5 amp
1.0 amp
0.75 amp
Minimum Load
20 mA ( 5mA)
20 mA
35 mA (5mA)
On State Drop
1.0 V, maximum
2.5 V, maximum 2.0 V, maximum
Surge Current
incandescent,
capacitive loads:
inductive loads:
3.5 amps, peak
7 amps for
20 msec
3.5 amps, peak
3 amps for
20 msec
3.5 amps, peak
3 amps for 20 msec
Output Leakage
single, fail-safe
module:
dual, fault-tolerant
modules:
5 mA, ( 700ua)
maximum
7.5 mA, (1 mA)
maximum
5.5 mA,
maximum
8.5 mA,
maximum
5.5 mA, (700ua)
maximum
8.5 mA, (1 mA)
maximum
T3481/81A
T3484
T3488/88A