beautypg.com

Rockwell Automation MHB44IND Pulse Input and Analogue Output Module User Manual

Pulse input and analogue output module, Mhb44ind)

background image

Triguard SC300E

MHB44IND

Pulse Input and Analogue Output

Module

(MHB44IND)

Issue 2 October 2005

INTRODUCTION

PURPOSE

The MHB44IND module (Figure 1-1) supports four pulsed voltage inputs for interfacing with field
detectors, and supplies 0 - 22mA analogue outputs for process control.

The module is a rack mounted, 9U high unit that provides the output control interface between
the SC300E processing environment and the user field environment. It has four current loop
output channels. All field inputs and outputs are galvanically isolated from the SC300E system
but have a common supply connection.

Circuit triplication and voting procedures make the module single-fault tolerant and latent
testing ensures that the failure of a channel will be recogised and reported to the SC300E
system. Front panel indicators show the state of the circuit ‘on-line’ status and the health of
the module. Sockets are provided on the front panel for monitoring the outputs.

The module is compatible with ‘dual slot hot repair’, and can be fitted in any of the ten I/O slots
in the SC300E chassis. ‘Wrong slotting’ is prevented by physical coding. The SC300E system
software identifies the module via a built-in hardware identifier.

Channel outputs leave the module via the DIN 41612 ‘rear plug-up’ system on the chassis
backplane.

This document is intended to provide a general understanding of the MHB44IND sufficient to
enable basic maintenance procedures to be effected in the field.

ASSOCIATED DOCUMENTATION

Reference No

Title

008-5097

Chassis User Manual

008-5201

TPH44AIC 4-Channel Pulse Input and Analogue Output Termination Card
User Manual