Assembly layout, Electrical specification, Sds-824x trusted – Rockwell Automation T824X Trusted Power System User Manual
Page 2: Industrial control system trusted, Power system-t824x

SDS-824X
Trusted
TM
Industrial Control System
Trusted
TM
Power system-T824X
ICS Triplex
Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-
www.icstriplex.com
ASSEMBLY LAYOUT
ELECTRICAL SPECIFICATION
Voltage Range – Input
90V ac to 264V ac
Voltage Range – Output
24Vdc or 28V dc (23-28 adjustable)
Frequency Range
47Hz to 63Hz
Inrush Current
50A max
Power Factor
0.95 min, 0.99 typical
Efficiency
78 – 84%
Hold-up Time
20ms min
Output Power
750W per Power Pack
Isolation voltage
3kVac, Primary to secondary
1.5kVac Primary or secondary to ground
MECHANICAL
SPECIFICATION
Dimensions (HxWxD):
43.5mm x 483mm x
340mm
(1.71ins x 19ins x
13.36ins)
Note: Optional support
bracket requires minimum
4U rack height. Unused
space may be populated
by other equipment.
Weight (fully populated)
10kg (approx.)
22lbs (approx.)
ENVIRONMENTAL
Operating Temperature:
0
°C to 60°C
(30
°F to 140°F)
Operating Humidity:
5 to 95%, non-
condensing
Vibration:
10 to 57Hz
±0.075mm
57 to 150Hz 1g
Shock:
15g, ½ sine wave, 11ms
EMI (IEC 801):
ESD
Air discharge to 15kV
Contact discharge to 8kV
Radiated Fields
10V/m, 27MHz to
500MHz
Transients and Bursts
2kV, 2.5kHz for
t=60 seconds