2. Installation

Trusted

TM

40 Channel 120Vac Digital Input FTA T8824 is designed to be mounted on either of the

TS32 or TS35 DIN rails in the horizontal or vertical positions as required.

3. Associated Cable Selection

Refer to the product descriptions detailed below:

PD-TC000

Trusted

TM

Power Cables

PD-TC200

Trusted

TM

I/O Companion Slot Cables

4. Cable Capacitance

With long field cables the capacitive coupling of the cable can cause a significant voltage to be seen at
the T8424 input when the field switch is open. This causes the T8424 to report that the field switch is
still on when it is turned off.

Revision E T8824 FTAs have lower loop resistance, which reduces the capacitive noise and increases
the available loop length.

The table below shows some estimated maximum lengths for different cables and mains supplies.
Practical distances will be less than this due to other noise and for switching safety margins.

Revision E

Earlier revisions

15pF/m, 110V, 50Hz

2940m

890m

30pF/m, 110V, 50Hz

1470m

470m

15pF/m, 110V, 60Hz

2450m

790m

30pF/m, 110V, 60Hz

1220m

390m

15pF/m, 120V, 50Hz

2620m

850m

30pF/m, 120V, 50Hz

1310m

420m

15pF/m, 120V, 60Hz

2190m

700m

30pF/m, 120V, 60Hz

1090m

350m

Table 1 Theoretical maximum cable lengths