Block diagram, Electrical specification, Sds-8480 trusted – Rockwell Automation T8480 Trusted TMR Analogue Output Module User Manual
Page 2: Industrial control system trusted, Tmr analogue output module-t8480, Ics triplex, Mechanical specification, Environmental, Ofiu hiu fpdu fpiu, Oftu

SDS-8480
Trusted
TM
Industrial Control System
Trusted
TM
TMR Analogue Output Module-T8480
ICS Triplex
Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-
www.icstriplex.com
BLOCK DIAGRAM
ELECTRICAL SPECIFICATION
Number of Outputs
40 Channels
No. of Independent Power Groups
5, each of 8outputs
Field Common Isolation
Sustained Working
±250V dc
Maximum Withstanding
±2.5kV dc
Output Current
Range
0.33-22mA
Output Current Rating
Continuous
22mA
Output Off Resistance (effective
leakage)
69k=
Step Response (10-90%)
10ms
Circuit Type
Fault tolerant, fully triplicated with
optional line monitoring
MECHANICAL
SPECIFICATION
Dimensions (HxWxD):
241mm x 30mm x 300mm
(9.5ins x 1.2ins x 11.8ins)
Weight:
1.13kg
(2.5lbs)
ENVIRONMENTAL
Operating Temperature:
-5
°C to 60°C
(23
°F to 140°F)
Operating Humidity:
5 to 95%, non-
condensing
Vibration:
10 to 57Hz
±0.075mm
57 to 150Hz 1.0g
Shock:
15g, ½ sine wave, 11ms
EMI (IEC 801):
ESD
Air discharge to 15kV
Contact discharge to 8kV
Radiated Fields
10V/m, 27MHz to
500MHz
Transients and Bursts
2kV, 2.5kHz for
t=60 seconds
Slice Power
Supply
Housekeeping
Failsafe Bias Control
A
Back Plane
Power Bus
1
Front Panel
T
M
R
In
te
rm
o
d
u
le
B
u
s
Opto Isolation Boundary
Serial Display Latches
Voted Status Display LEDs
Internal Voting Bus
Housekeeping
Module Temp
Supply Diag
DSP reference
Health
Indicators
Back Plane Power Bus 1
Back Plane Power Bus 2
Slice A
OFIU
HIU
FPDU
FPIU
Field Logic
Control
Redundant Supply
N.C.
N.O.
Diagnostic
Monitor
Bus
Interface
Bus
Interface
Slice Power
Supply
Housekeeping
Failsafe Bias Control
B
Field Logic
Control
N.C.
N.O.
Diagnostic
Monitor
Slice Power
Supply
Housekeeping
Failsafe Bias Control
C
Field Logic
Control
N.C.
N.O.
Diagnostic
Monitor
Bus
Interface
Front Panel
Voting Logic
Slice
Control
B
Time Stamp
Slice
Control
B
Time Stamp
Slice
Control
A
Time Stamp
OFTU
+V
Slice B
Slice C
A
B
C
Group
Fail-Safe
Switch
-
V
Field Interface
Protection Circuit