TM
Power Distribution Unit 15-Way Fused-T8293
ICS Triplex
Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-
www.icstriplex.com
BLOCK DIAGRAM
ELECTRICAL SPECIFICATION
Voltage Range
22-30V dc or 43-60V dc (link selectable)
Supply Current
23A maximum
Supply Connection
LU10.16 screw clamp terminal
Supply Conductor Clamping
Range -
solid
stranded
AWG Conductors
0.5 to 16mm
2
0.5 to 10mm
2
No. 22…8
Input Power Supply Indication
2-off green LEDs
Output Indication
30-off red LEDs indicating individual
failed fuses
Fused Outputs
30 arranged in two banks of 15
Fuse Type
3A 5x20mm cartridge
Leakage Current (failed fuse)
0.6mA @ 30V dc or 1.2mA @ 60V dc
maximum
Output Connector
BLZ 2-part terminal
Output Conductor Clamping
Range
0.5 to 2.5mm
2
AWG Conductors 28...14
Common Alarm Output
Volt-free contact – powered, closed in
healthy state
Maximum Switching Voltage
60V dc or 125V ac @ 0.5A
Minimum Load
5V @ 1mA
MECHANICAL
SPECIFICATION
Dimensions (HxWxD):
79mm x 285mm x 109mm
(3.1ins x 11.2ins x 4.3ins)
Weight:
576g
(1.3lbs)
ENVIRONMENTAL
Operating Temperature:
-5
°C to 60°C
(23
°F to 140°F)
Operating Humidity:
5 to 95%, non-condensing
Vibration:
10 to 57Hz
±0.075mm
57 to 150Hz 1.0g
Shock:
15g, ½ sine wave, 11ms
EMI (IEC 801):
ESD
Air discharge to 15kV
Contact discharge to 8kV
Radiated Fields
10V/m, 27MHz to
500MHz
Transients and Bursts
2kV, 2.5kHz for
t=60 seconds