Rockwell Automation T3464 ICS Regent AC Guarded Digital Output Module User Manual
Ics regent, Ac guarded digital output module, 110 vac
ICS Regent
®
PD-6021
Industrial Control Services
1
AC Guarded Digital Output Module
110 VAC
(T3464)
Issue 1, March, 06
AC Guarded digital output modules provide guarded
switching of user-supplied 110 AC voltages to a maximum of
sixteen field loads. These modules are called Guarded
because no single fault within a module will inadvertently
apply power to an output. Extensive fault detection and
critical redundant circuits ensure that the module operates in
a fail-safe manner.
Features
·
Sixteen Guarded output circuits configured as two separately
powered groups of eight circuits each.
·
Fault tolerant operation when connected in parallel with
another module of the same type.
·
Hot-replaceable.
·
100% self-test of all critical circuits.
·
Zero-cross load switching.
·
Individual front panel indicators on each module show
active/fault and output on/off status (field side). A diagnostic
message display provides additional status indicators.
·
Fuses accessible from front panel.
·
2500 volt minimum electrical isolation between field and logic
circuits.
·
TÜV certified, Risk Class 5, see Safety Considerations.
Two Guarded output modules can be connected in parallel to
obtain fault tolerant control of power to loads. In this parallel
module configuration, either module can be removed and