Monitored Digital Input Modules, Type F (T7411F, T7418F)
2 0
Industrial Control Services
represent the voted value of the two inputs. This variable
would be used elsewhere in the application program to
represent the status of the field input in the associated safety
interlock logic.
When both input modules are healthy, both inputs must turn
off to turn off the voted result and initiate a trip. Because the
inputs are normally energized, the voted result is normally
on. If a fault occurs on one of the input modules, the voted
result will remain on, eliminating a nuisance trip. Automatic
testing of the input module will detect the fault and the
associated fault bit will be turned on, leaving the voted result
under the control of the remaining healthy input module.
The faulted module can be removed and replaced. After
replacing the input module and performing a voted reset, the
fault bit is turned off, restoring the input configuration to the
dual mode.
Normally De-Energized Inputs
Figure 13 shows a ladder logic rung that would be suited for
normally de-energized inputs that energize to trip.
Figure 13. Dual Voting for Normally De-Energized Inputs.
In this example the variables represent the same status
information as described above for normally energized inputs.
When both input modules are healthy, both inputs must turn
on to turn on the voted result and initiate a trip. Because the
inputs are normally de-energized, the voted result is normally
off. If a fault occurs on one of the input modules, the voted
result will remain off, eliminating a nuisance trip. Automatic
testing of the input module will detect the fault and the
associated fault bit will be turned on, allowing the voted result
to be controlled by the remaining healthy input module. The
faulted module can be removed and replaced. After replacing