8 XM-940 Dynamic Measurement Terminal Base

Publication

GMSI10-IN020C-EN-P - October 2013

Power Requirements

Refer to the XM-124 Standard Dynamic Measurement installation guide,
publication

1440-IN001

, for specific power consumption and other

requirements.

Refer to the XM Power Supply Solutions Application Technique, publication

ICM-AP005

, for additional details.

Interconnect Limit

Total current draw through the side connector cannot exceed 3 A. A separate
power connection is necessary if the total current draw of the interconnecting
modules is greater than 3 A.

IMPORTANT

There are no drawings associated with the XM-124 Standard Dynamic
Measurement Module, catalog number 1440-SDM02-01RA. Be sure that
the installer follows all applicable local and regional requirements for
installation of the product in the planned location and environment.

TIP

If the total current draw for a row of modules is greater than 3 A, consider
connecting power to a module near the center of the rail, rather than at a
module on either end. Insure that there is less than 3 A load in either direction
from the module where power is connected.