Rockwell Automation T812X Trusted Processor Interface Adaptor Module User Manual
Sds-t812x trusted, Industrial control system trusted, Processor interface adaptor module - t812x
![background image](/manuals/581038/1/background.png)
SDS-T812X
Trusted
TM
Industrial Control System
Trusted
TM
Processor Interface Adaptor Module - T812X
Issue 5 Jan 2006
DESCRIPTION
The Trusted
TM
Processor Interface Adaptor T812X provides easy access to
the communications ports of the Trusted
TM
TMR Processor in the Trusted
TM
Controller Chassis for Peer to Peer communications, DCS and other links,
networked PCs etc. The Adaptor also supports fault/fail and diagnostics
connections to the Processor, and connection facilities for IRIG B time
Synchronisation facilities, as well as enabling the user of Modbus Master
facilities on the T8151 Communication Interface Card.
The Adaptor comprises a printed circuit board (PCB) on which the
communications ports are mounted. The PCB also supports two 48-way
DIN41612 E-type connectors which enables the Adaptor to be plugged into
the Trusted
TM
TMR Processor Module input/output (I/O) connectors (Active
and Standby) at the rear of the Trusted
TM
Controller Chassis. The
communications ports available from the Adaptor are RS485 (Port 1) and
RS422/485 (Ports 2 and 3). The Ports are accessed via Phoenix contact
2.5mm pitch connectors.
Fault/fail, diagnostic and PSU shutdown monitor, and IRIG B time
Synchronisation signals are also available via Phoenix connectors.
A complete set of connectors mentioned above are allocated to both the
Active and Standby processors.
Termination resistors for RS422/485 communications are selectable via
links. These are mounted on the PCB and are the only configurable items
which require setting up before using the Adaptor.
When the Adaptor is plugged into
the I/O connector on the rear of
the Trusted
TM
Controller Chassis,
it is mechanically latched in
position. Release buttons are
provided to enable the user to
unplug the Adaptor as required.
FEATURES
Allows easy access for
external systems to
communicate with a
Trusted
TM
System
Easy installation (connects
directly onto the I/O
connector at the rear of the
processor)
Two RS422/485
connections
One RS485 connection
Fault/fail connections for
Active and Standby
Processors
Processor diagnostics
connection
PSU shutdown monitor
connections
Connection facilities for
IRIG B122 and IRIG B002
time Synchronisation
signals
Modbus Master enabling of
the T8151B Communication
Interface Card