Block diagram, Electrical specification, Sds-8800 trusted – Rockwell Automation T8800 Trusted 40 Channel 24Vdc Digital Input FTA User Manual
Page 2: Industrial control system trusted, Ics triplex, Mechanical specification

SDS-8800
Trusted
TM
Industrial Control System
Trusted
TM
40 Channel 24V dc Digital Input FTA -T8800
ICS Triplex
Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-
www.icstriplex.com
BLOCK DIAGRAM
Figure 2
ELECTRICAL SPECIFICATION
Number of Field Inputs
40
Internal Use Inputs
2
Type of Input Terminals
MKKDS 3
Type of Power Terminals
MVSTBR 2.5
Acceptable Wire Sizes
UL
CSA
30-12 AWG 15A 300V
28-12 AWG 10A 300V
DIN Rail Compatibility
EN 50022
NS 35/7.5
NS 35/15
NS 32
Current Limiting
On-board resistor or fuse
Testing
100% electrical (continuity and
short-circuit)
Intrinsic Safety
External barrier
MECHANICAL
SPECIFICATION
Dimensions (HxWxD):
335mm x 111mm x 51mm
(13.2ins x 4.4ins x 2ins)
Weight:
0.9kg (2.0lbs)
ENVIRONMENTAL
Operating Temperature:
-5
°C to 60°C
(23
°F to 140°F)
Operating Humidity:
5 to 95%, non-condensing
Vibration:
10 to 57Hz
±0.075mm
57 to 150Hz
1.0g
Shock:
15g, ½ sine wave, 11ms
EMI (IEC 801):
ESD
Air discharge to 15kV
Contact discharge to 8kV
Radiated Fields
10V/m, 27MHz to 500MHz
Transients and Bursts
2kV, 2.5kHz for t=60 seconds
+V 1
+V 2
0 V
SK1
TB2
TB1
TB3
To I/O
Module
Channels 0 & 41 reserved for internal use
Typical Input
Channel
Schematic
Field
Inputs
Current Limiting
Resistor or Fuse
Dual Loop Power
3 - 40
1
2