ICS Regent+Plus

®

PD-7017

Industrial Control Services

1

Relay Output Modules

Low Power and High Power

(T7446L and T7446H)

Issue 1, March, 06

Relay output modules provide control of eight user output
loads. Two types of relay output modules are available
providing dry contact relay closure outputs for switching a
variety of AC and DC voltages to field loads. Each module's
triplicated I/O Safetybus interface ensures that no Regent
system failure can incorrectly apply power to an output and
that no failure in the module can affect the operation of the
Regent system or other I/O modules in the system.

Features

·

Eight isolated, dry contact relay outputs: four Form-C, and four

form-A or Form-B selectable.

·

Hot replaceable.

·

Automatic self-testing of triplicated I/O Safetybus circuits and

many simplex logic circuits.

·

High power modules (T7446H) operate up to 250 VAC/125

VDC switching loads rated at 500 VA or 100 Watts.

·

Low power modules (T7446L) operate up to 125 VAC/VDC

switching loads rated at 60 VA or 30 Watts.

·

Individual front panel indicators on each module show active

and fault status, shutdown state, and output status (logic
side).

·

TÜV certified, Risk Class 5, non-interfering.