Block diagram, Single channel schematic, Electrical specification – Rockwell Automation T8833 Trusted 20 Channel Analogue/Digital Isolated Input FTA User Manual
Page 2: Sds-8833 trusted, Industrial control system trusted
![background image](/manuals/580979/2/background.png)
SDS-8833
Trusted
TM
Industrial Control System
Trusted
TM
20 Channel Analogue/Digital Isolated Input FTA - T8833
ICS Triplex
Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-
www.icstriplex.com
BLOCK DIAGRAM
Single Channel Schematic
ELECTRICAL SPECIFICATION
Field Current Loop (Per Channel)
2 to 30mA
Field Loop Volt Drop at 20mA
9.5V
Recommended Operating Current
2 to 20mA per channel
Power Consumption (Field Loop)
19mW maximum
MECHANICAL
SPECIFICATION
Dimensions (HxWxD):
120mm x 336mm x 50mm
(4.7ins x 13.2ins x 2 ins)
Weight (fully populated)
500gms
(1.1lbs)
ENVIRONMENTAL
Operating Temperature:
-5
°C to 60°C
(23
°F to 140°F)
Operating Humidity:
5 to 95%, non-
condensing
Vibration:
10 to 57Hz
±0.075mm
57 to 150Hz 1.0g
Shock:
15g, ½ sine wave, 11ms
EMI (IEC 801):
ESD
Air discharge to 15kV.
Contact discharge to 8kV
Radiated Fields
10V/m, 27MHz to
500MHz
Transients and Bursts
2kV, 2.5kHz for
t=60 seconds
TB1 A
TB1 B
100R
7V5
CON1 VPOWER
CON1 COMMON
CON1 VSENSE
+