Block diagram, Electrical specification, Sds-8444 trusted – Rockwell Automation T8444 Trusted Pulse Generator and Monitoring Module User Manual
Page 2: Industrial control system trusted, Pulse generator and monitoring module-t8444

SDS-8444
Trusted
TM
Industrial Control System
Trusted
TM
Pulse Generator and Monitoring Module-T8444
ICS Triplex
Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-
www.icstriplex.com
BLOCK DIAGRAM
ELECTRICAL SPECIFICATION
Number of channels
Pulse output - 12
Pulse Input - 24
Control Signals - 4
Field common Isolation
Sustained working - +/- 250Vdc
Max withstanding - +/- 2.5KVdc
Input measurement range -20 to +28V
Input Impedance
50K ohms
Accuracy
0.01%
Sequence of events
Resolution - 1ms
Output turn on/off delay
1.0ms
Circuit type
Fault tolerant, fully triplicated with optional
line monitoring
Power consumption
22W
MECHANICAL
SPECIFICATION
Dimensions HxWxD mm (inches):
241 x 30 x 300
(9.5 x 1.2 x 11.8)
Weight
1.3kg (approx.)
2.9lbs (approx.)
Environmental
Operating Temperature:
-5°C to 60°C
(23°F to 140°F)
Operating Humidity:
5 to 95%, non-condensing
Vibration:
10 to 57Hz
±0.075mm
57 to 150Hz 1g
Shock:
15g, ½ sine wave, 11ms
EMI (IEC 801):
ESD
Air discharge to 15kV
Contact discharge to 8kV
Radiated Fields
10V/m, 27MHz to
500MHz
Transients and Bursts
2kV, 2.5kHz for
t=60 seconds