beautypg.com

Rockwell Automation GV6000 Fan/Fan Transformer Replacement - Frame 6 User Manual

Fan/fan transformer replacement – frame 6, Installation instructions

background image

Installation Instructions

Optional

Communications

Module

L2

L1

T3

T2

T1

L3

INPUT

OUTPUT

USE 75 C

COPPER WIRE

ONLY

TORQUE
52 IN-LB

(6 N-M)

BR2

PS+

PS–

BR1

DC+

DC–

USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)

22-10
AWG

5.3 IN-LB
(0.6 N-M)

WIRE STRIP

2

0V

0V

DC–

DC+

Fan/Fan Transformer Replacement – Frame 6

1

L1

L2

L3

O

I

=

A. Remove the screws that secure the right-side drive

enclosure panel. Remove panel.

B. Remove the screws that secure the terminal block

rail.

C. Gain access to the four transformer screws by

repositioning the terminal block rail and terminal
label sheet. See

Figure 1

.

D. Disconnect transformer wires.

E. Remove the screws securing the transformer.

Remove the transformer. If the transformer
incorporates a jumper, note placement and correctly
position jumper on new transformer.

F. Position and secure new transformer to chassis with

screws previously removed. Re-assemble drive in
reverse order. All screws should be tightened to 3.2
N-m (28 lb.-in.).

Figure 1