Analog Input Modules (T3420A, AF)
P D - 6 0 2 3 M a r - 0 6
25
Table 5. Slot Key Positions.
Module
Upper
Connector
Lower
Connector
T3420A
9
15
T3420AF
9
15
Configuration
Each input module is configured using the W
INTERPRET
I/O
Configuration Editor. In the editor, you will perform the
three steps described below to configure the input module.
1) Set the Module Type:
Position the cursor on the module slot you wish to define.
Choose Set Module Type from the Edit Menu and select
the appropriate analog input module from the list.
There are four different analog input module types listed
in the Set Module Type dialog. Be sure to select the
appropriate module, i.e. standard response (T3420A) vs.
fast response (T3420AF) and single-ended (16-channel) vs.
differential (8-channel).
2) Edit the Module Definition:
Choose Edit Module Definition from the Edit Menu. A
dialog box will open where you can define the input point
definitions. Single-ended analog input modules will show
sixteen points that you can configure, while differential
analog input modules will show eight points that you can
configure.