beautypg.com

Trusted – Rockwell Automation T80016 Application Note Maintenance Override Programming User Manual

Page 11

background image

Trusted

TM

AN-T80016 Maintenance Override Programming

Issue 1 June 08

AN-T80016

11

The safety signal is set active (False) when the real input is active (False) and
the maintenance override is not active. The safety signal is cleared (True) when
Reset is active (True) and either the input is not active or the Maintenance
Override is active.

*)

IF

RST

AND

(DI

OR

Int_OS)

THEN

TRIP :=

True

;

(* Trip can be reset *)

END_IF;

IF

NOT

DI

AND

NOT

Int_OS

THEN

TRIP :=

False

;

(* Input tripped and not overridden *)

END_IF

;