Power wiring, Control wiring, Terminal assignments – Rockwell Automation SP600 Quick Start 20-150HP User Manual
Page 2: Reference wiring, Analog reference wiring (0 to 10 vdc input), Analog output wiring (0 to 10 vdc input), Two wire start/stop control, Three wire start/stop control, Stop start

Power Wiring
Input Voltage: Determined by model
number. Voltage Class configures the drive
for International voltage supplies.
Control Wiring
Default:
(Out-of-the-box) configuration is
for Keypad control. The user will be able
to start the controller from the drive
mounted operator interface module (OIM).
Speed adjustment using UP/DOWN keys
while in Monitor Display mode.
Stop Start
L1
R
L2
S
L3
T
+DC BRK T1
U
T2
V
T3
W
PE
PE
M
BR1 BR2
ATTENTION: The SP600 does not
provide branch circuit protection.
The user must install the proper
protection devices.
!
24
25
26
28
Supply
Com.
Logic
Com.
+24
VDC
Terminal Assignments
Term.#
Signal Name
Default
1
Analog Volts In1 (-)
2
Analog Volts In1 (+)
Not Assigned
3
Analog Volts In2 (-)
Default 0-10 VDC
4
Analog Volts In2
(+)
5
Reference Common
6
Analog Volts Out1
(-)
Output Frequency
7
Analog Volts Out1
(+)
See Param. 342
8
Analog Current Out1(-)
Not Assigned
9
Analog Current Out1(+)
10
Reserved
11
Digital Out1 - NC
Fault*
12
Digital Out1 - C
13
Digital Out1 - NO
14
Digital Out2 - NC
Running*
15
Digital Out2 - C
16
Digital Out2 - NO
17
Analog Current In1
(-)
Default 4-20 mA
18
Analog Current In1
(+)
19
Analog Current In2
(-)
Not Assigned
20
Analog Current In2
(+)
21
-10 VDC Ref. Out
Speed Potentiometer
22
+10 VDC Ref. Out
23
Reserved
24
+24 VDC Output
24 V logic supply
25
Logic Input Common Logic Common
26
24 V Int. Common
Logic Common
27
Digital In 1
Stop/Clear Fault
28
Digital In 2
Start
29
Digital In 3
Function Loss
30
Digital In 4
Jog
31
Digital In 5
Manual
32
Digital In 6
Speed Select 1
D-2991
Reference Wiring
Analog Reference Wiring
(0 to 10 VDC Input)
(P90) Speed Ref A Sel = Analog In1
(P91) Speed Ref Hi = 60 Hz.
(P92) Speed Ref Lo = 0 Hz.
(P320) Analog In Config =..xx00
(P322) Analog In 1 Hi = 10.0 V
(P323) Analog In 1 L0 = 0.0 V
Analog Inputs can be configured for 4-20
mA. See instruction manual.
Analog Output Wiring
(0 to 10 VDC Input)
(P341) Analog Out Absolute = 1
(P342) Analog Out1 Sel = Output Freq.
(P343) Analog Out1 Hi = 10.0 V
(P344) Analog Out1 Lo = 0.0 V
1 2 5 22
Analog In 1 (-)
Common
Analog In 1 (+)
+10 VDC
3
4
5
6
7
8
-
+
CommonA Out
Volts
0-10 VDC
Control Wiring
Two Wire Start/Stop Control
(P89) Logic Source Sel = Terminal Block
(P361) Digital In1 Sel = Not Used
(P362) Digital In2 Sel = Run
(P363) Digital In3 Sel = Function Loss
Three Wire Start/Stop Control
(P89) Logic Source Sel = Terminal Block
(P361) Digital In1 Sel = Stop
(P362) Digital In2 Sel = Start
(P363) Digital In3 Sel = Function Loss
See Parameters P361 to P366 for
configuration of all logic inputs.
24 25 26 27 28 29
Run
Function Loss
Supply Com.
Logic Com.
+24 VDC
24 25 26 27 28 29
Run
Function Loss
Supply Com.
Logic Com.
+24 VDC
Stop
* Form C Relay contact outputs:
NO (Normally Open)
NC (Normally Closed)
C (Common)