Rockwell Automation 20B MOV Replacement Kit User Manual
Mov replacement kit - frame 5, Installation instructions, L1 l2 l3
Installation Instructions
Optional
Communications
Module
L2
L1
T3
T2
T1
L3
INPUT
OUTPUT
USE 75 C
COPPER WIRE
ONLY
TORQUE
52 IN-LB
(6 N-M)
BR2
PS+
PS–
BR1
DC+
DC–
USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)
22-10
AWG
5.3 IN-LB
(0.6 N-M)
WIRE STRIP
2
0V
0V
DC–
DC+
3
MOV Replacement Kit - Frame 5
1
L1
L2
L3
O
I
=
A. Locate the MOV assembly. Note wire placement
and remove the 4 wires/lugs from the terminal
block. Remove the screw that secures the MOV to
the chassis. See
Figure 1
.
B. Compare lug styles between the MOV just removed
and the new one.
– If the lugs are identical, install the new MOV in
reverse order. Verify correct wire placement and
tighten the MOV screw to 3.2 N-m (28 lb.-in.).
– If the lugs are different,
cut the lugs off of the new
MOV (as close to the lug
as possible). Strip the
insulation from each lead
approximately 8 mm
(0.31 in.). Crimp the
supplied lugs to the wires.
Install the new MOV in
reverse order. Verify
correct wire placement
and tighten the MOV screw to 3.2 N-m (28 lb.-
in.).
Figure 1 MOV Assembly (Frame 5 shown)
8 (0.31 in.)
WIRE RANGE: 14-1/0 AWG (2.5-35 MM
2
)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY
POWER TERMINAL RATINGS
WIRE RANGE: 6-1/0 AWG (16-35 MM
2
)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)
GROUND TERMINAL RATINGS (PE)
300 VDC EXT PWR SPLY TERM (PS+, PS-)
WIRE RANGE: 22-10 AWG (0.5-4 MM
2
)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)
17
21
INPUT AC
OUTPUT
Optional
Communications
Module
9