5. Link Assignments

The functions of the links are detailed below.

5.1. Two Wire Operation

The links listed in the table below must be fitted for 2-wire operation. The RTD FTA defaults to 3-wire
operation if the links detailed are not fitted.

Channel

Link

1

LK93

2

LK89

3

LK94

4

LK90

5

LK95

6

LK91

7

LK96

8

LK92

Table 4 Two Wire Link Assignments

5.2. Voltage Output

The links listed in the table below must be fitted for voltage output. The RTD FTA defaults to current
output operation if the links detailed are not fitted.

Channel

Link

1

LK1

2

LK45

3

LK2

4

LK46

5

LK3

6

LK47

7

LK4

8

LK48

Table 5 Voltage Output Link Assignments