Rockwell Automation 2099-BM-xxx Remove Jumpers in Kinetix 7000 Drives User Manual
Remove jumpers in kinetix 7000 drives, Quick reference

Publication 2099-QR003A-EN-P — October 2008
328028-P02
Supersedes Publication 2099-PA001A-EN-P — May 2006
Copyright © 2008 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Kinetix is a trademark of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Quick Reference
Remove Jumpers in Kinetix 7000 Drives
Catalog Numbers 2099-BM06-S, 2099-BM07-S, 2099-BM08-S,
2099-BM09-S, 2099-BM10-S, 2099-BM11-S, 2099-BM12-S
This document provides information regarding the protective metal oxide
varistors (MOVs) and common mode capacitors in the Kinetix 7000 drives.
The MOVs, capacitors, and a sticker describing this issue, are located within
the power terminal block. Refer to the Kinetix 7000 High Power Servo Drives
Installation Instructions, publication
ATTENTION
Kinetix 7000 drives contain protective MOVs and common mode
capacitors that are referenced to ground. In a grounded power
distribution system, these devices assist in isolating the drive
from electromagnetic interference (EMI).
These devices must be disconnected if the drive is installed in:
• unbalanced, ungrounded, or resistive-grounded power
distribution systems.
•
common bus configurations.