beautypg.com

Wire the ac line filter, Figure 1 wiring example for the ac line filter, Ipd connector wiring specifications – Rockwell Automation 2097-Fx AC Line Filter Installation Instruction User Manual

Page 6

background image

6 Bulletin 2097 AC Line Filters

Publication 2097-IN003D-EN-P - November 2011

Wire the AC Line Filter

Connect the AC line filter as shown in these examples. Refer to the System Design for Control
of Electrical Noise Reference Manual, publication

GMC-RM001,

for proper high-frequency

(HF) bonding techniques to improve overall system performance.

Figure 1 Wiring Example for the AC Line Filter

TIP

Replacement connector sets (catalog number 2097-CONN1) are available. Sets include
general purpose power input (IPD) header, back-up power (BP) header, shunt resistor and DC
bus (BC) header, motor power (MP) header, and safe torque off (STO) header.

IPD Connector Wiring Specifications

Cat. No.

Input Power

Connects to Terminals

Recommended
Wire Size
mm

2

(AWG)

Strip Length
mm (in.)

Torque Value
N•m (lb•in)

Pin

Signal

2097-F1
2097-F2
2097-F4
2097-F5
2097-F6

240/480V AC

IPD-1
IPD-2
IPD-3
IPD-4

PE
L1
L2
L3

14 AWG (2.5mm

2

)

7 (0.28)

0.5 (4.5)

L3

L2

L1

IPD-4 (L3)

IPD-3 (L2)

IPD-2 (L1)

IPD-1 (PE)

L3’

L2’

L1’

PE

240/480V

Bonded Cabinet
Ground Bar

AC Line Filters

Input Fusing

Line, AC Mains

Kinetix 300 Drive
Input Power (IPD)
Connections

Line

Load

Ground Terminals