Understand system planning – Rockwell Automation 1797-PS1E FLEX Ex 85-253V AC In/Quad-Ex DC Out Power Supply User Manual
Page 4
4 FLEX Ex 85…253V ac In/Quad-Ex dc Out Power Supply
Publication
1797-5.33 - April 2007
The 1797-PS1E is an 85…253V ac in/quad-Ex dc out power supply in a
flame-proof enclosure with increased safety input/output terminations. The
85…253V ac gland is an M20 x 1,5 and can accept a cable from 6…12 mm
(0.267…0.472 in.) in diameter. The Ex outputs are M16 x 1,5 and can accept a
cable from 4…8 mm (0.157…0.315 in.) in diameter.
Features include the following:
• 85…253V ac supply source
• Four channels, 8.5 W output each channel
• Outputs are IS galvanically isolated from the source
• All channels are independently IS limited
Understand System Planning
Part of system planning is determining what modules are needed for the
application, how many power supplies are needed, how to best partition the
system, and where to locate the system cabinets.
A key task in the development cycle is determining the number of power
supply outputs (thus power supplies) you will need. In the following example,
you will need 11 power outputs if you are using the fiber hub, which requires
8.5 W.
Each power supply has four independent IS-power outputs capable of 8.5 W
each. In the above example, we required 11 IS-power outputs so 3 power
supplies were sufficient.
Modules
Requires
Modules
Requires
Fiber hub
8.5 W
Two thermocouple inputs
1.6 W each
Two ControlNet adapters
8.5 W each
Two digital outputs
7.5 W each
Two analog inputs
7.5 W each
Three NAMUR digital inputs
2.8 W each
Two analog outputs
6.3 W each
Two counter inputs
4.25 W each