Rockwell Automation 2198-KITCON-DSL Kinetix 5500 Feedback Connector Kit Installation Instructions User Manual
Kinetix 5500 feedback connector kit, Installation instructions, About the feedback connector kit
Installation Instructions
Kinetix 5500 Feedback Connector Kit
Catalog Number 2198-KITCON-DSL
About the Feedback Connector Kit
This feedback connector kit includes a two-pin connector plug that accepts feedback wires from
the 2090-CS
xM1DF-xxAAxx single motor cable. You must assemble the bottom half of the
connector housing with the connector plug wired and properly positioned. In addition, you must
align the cable shield and insulation. The housing cover includes a grounding plate, and when
mated with the bottom half, provides a high-frequency bond with the cable shield.
Refer to the Kinetix® 5500 Servo Drives User Manual, publication
information.
Install the Feedback Connector Kit
10
(0.39)
8
(0.31)
25
(0.98)
Follow these steps to assemble the connector kit.
1. Insert wires into plug (observe polarity).
2. Position connector plug as shown.
3. Align braided shield as shown to maximize contact
for high-frequency bond.
4. Align outer insulation of feedback cable as shown
for proper strain relief.
5. Fit cover tab into bottom-half mating feature,
keeping the plug pushed forward past retention rib
as the cover is closed.
6. Tighten cover screws to recommended torque.
Cover should close with no gaps.
Pressure on the end of connector plug should not
push plug back into connector housing.
Feedback Cable Preparation, mm (in.)
Grounding Plate
Housing
Cover
Connector
Plug
Connector Housing
(bottom half)
EPWR+, Blue
EPWR-, White
Position cable shield here for optimum
bond with grounding plate.
Position cable insulation here for proper strain relief.
Cover Tab
Retention Rib
Mounting Screws (2)
Connector Plug
Removed