Rockwell Automation 2198-KITCON-DSL Kinetix 5500 Feedback Connector Kit Installation Instructions User Manual

Kinetix 5500 feedback connector kit, Installation instructions, About the feedback connector kit

background image

Installation Instructions

Kinetix 5500 Feedback Connector Kit

Catalog Number 2198-KITCON-DSL

About the Feedback Connector Kit

This feedback connector kit includes a two-pin connector plug that accepts feedback wires from
the 2090-CS

xM1DF-xxAAxx single motor cable. You must assemble the bottom half of the

connector housing with the connector plug wired and properly positioned. In addition, you must
align the cable shield and insulation. The housing cover includes a grounding plate, and when
mated with the bottom half, provides a high-frequency bond with the cable shield.

Refer to the Kinetix® 5500 Servo Drives User Manual, publication

2198-UM001

, for more

information.

Install the Feedback Connector Kit

10

(0.39)

8

(0.31)

25

(0.98)

Follow these steps to assemble the connector kit.

1. Insert wires into plug (observe polarity).
2. Position connector plug as shown.
3. Align braided shield as shown to maximize contact

for high-frequency bond.

4. Align outer insulation of feedback cable as shown

for proper strain relief.

5. Fit cover tab into bottom-half mating feature,

keeping the plug pushed forward past retention rib
as the cover is closed.

6. Tighten cover screws to recommended torque.

Cover should close with no gaps.
Pressure on the end of connector plug should not
push plug back into connector housing.

Feedback Cable Preparation, mm (in.)

Grounding Plate

Housing

Cover

Connector

Plug

Connector Housing
(bottom half)

EPWR+, Blue
EPWR-, White

Position cable shield here for optimum
bond with grounding plate.

Position cable insulation here for proper strain relief.

Cover Tab

Retention Rib

Mounting Screws (2)

Connector Plug

Removed