beautypg.com

Before you begin – Rockwell Automation 2090-CNSxxx Kinetix 6000M Series A Network Communication Cable Installation Instructions User Manual

Page 3

background image

Kinetix 6000M Series A Network Cable 3

Publication 2090-IN034B-EN-P - March 2012

Before You Begin

Remove all packing material from within and around the item. After unpacking, verify the
catalog number against the purchase order, and visually inspect the cable and each
connector for damage. If necessary, immediately notify the carrier of any shipping
damage.

Cables are stored and shipped in a coil, and will retain this shape unless you straighten the
cable. To straighten a cable, hang a short cable from its mid-point or lay a long cable on
the floor in a straight line. Any coiling that persists should relax within 24 hours. Doing
this results in a cable that is easier to install.

Observe the following precautions when installing the cables in a servo system. Failure to
observe these safety notices could result in personal injury or damage to the motor and
equipment.

SHOCK HAZARD: To avoid the hazard of electrical shock, be sure to ground any cable providing
power at a minimum of one point. To prevent the build-up of electrical energy, factory-supplied
cables use one of these grounding techniques:

Bond the overall shield to the connector housing.

Make sure there is a direct connection-to-ground for each cable shield.

Connect an exposed cable braid or a ground wire, if present, to the power cable clamp,
housing, or another suitable chassis ground.

Failure to observe these safety procedures could result in personal injury or equipment damage.

ATTENTION: Arcing or unexpected motion can occur if cables are connected or disconnected while
power is applied to the IDM system. Before working on an IDM system, disconnect power and wait
the full time interval as indicated in the warning on the IPIM module or verify the DC bus voltage at
the IPIM module measures less than 50V DC.

Failure to observe this precaution could result in severe bodily injury or loss of life, and damage to
the product will occur.

ATTENTION: The maximum length of cabling between the IPIM and the last IDM unit in the
system must not exceed 100 m (328 ft). Also, a maximum of two extension cables may be
connected between an IDM unit and the preceding IPIM module or IDM unit.

ATTENTION: The examples in this publication show the available connections, some of which may
not be appropriate for your specific installation. Refer to your system level installation instructions
or user manual for recommended wire trim lengths, and wiring examples appropriate to your
application.

Do not connect unused wires. Trim and finish unused wires to prevent accidental contact with
other wires or wire shields, or with a ground connection.

Failure to observe these safety procedures could result in personal injury or damage to the motor
and equipment.