Rockwell Automation 5000 Blue Line User Manual
Installation instructions—photoswitch, Series 5000 blue line
1
Installation Instructions—PHOTOSWITCH
R
Series 5000 Blue Line
All Sensors
Retroreflective
Polarized Retroreflective
Standard Diffuse
Fixed Focus Diffuse
Wide Angle Diffuse
Glass Fiber Optic
Plastic Fiber Optic
1
Sensing Distance
10m (33ft)
6m (20ft)
0.4m--2.1m (16in--7ft)
(IR) 127mm (5in) max peak @ 3in
(VR) 101.6mm (4in) max peak @ 2in
(IR) 508mm (20in)
(VR) 177.8mm (7in)
Depends on fiber optic cable
2
Transmitting LED
Infrared 880nm
Visible red 660nm
Infrared 880nm
(42DRA) Infrared 880nm (42DRF) Visible Red 660nm
Infrared 880nm
Visible red 660nm
3
Indicators
Red: Output
4
Field of View
2.5_
3.0_
—
—
Depends on fiber optic cable
5
Sensitivity Adjustment
Yes
6
Operating Temperature
--40_C to +65_C (--40_F to +150_F)
7
Relative Humidity
90% maximum
8
Housing/Lens Material
Valox
/Acrylic
Valox
/Glass
Valox
/Acrylic
9
Cover Gasket Material
Nitrile
10
Operating Environment
NEMA 3, 4, 12, 13, and IP66 (IEC 529), corrosion resistant, high-impact housing
11
Approvals
UL listed, CSA certified (except cable style power base), and CE marked for all applicable directives
12
Protections
Reverse Polarity/Power on False Pulse protection
13
Vibration
10--55 Hz, 1 mm amplitude, Meets or exceeds IEC 947--5--2
14
Shock
30G, Meets or exceeds IEC 947--5--2
Photohead with NPN and PNP Output
15
Catalog Number
42DRU--5000
42DRU--5200
42DRP--5000
42DRA--5000--FF
42DRA--5000--WA
42DRA--5000--FO
42DRF--5000--FO
42DRF--5000--FF
42DRF--5000--WA
16
Output Energized
LO/DO Selectable
17
Load Current
100mA
18
Leakage Current
1A
19
Response Time
1ms
Base
Terminal Base
Cable Base
15
Catalog Number
42DTB--5000
42DCB--5000
20
Supply Voltage
10--30V DC
21
Power Consumption
35mA