The entity concept allows interconnection of intrinsically safe apparatus
with associated apparatus not specifically examined in combination as a
system when the approved values of V
oc
and I
sc
of the associated apparatus are
less than or equal to V
max
and I
max
of the intrinsically safe apparatus and the
approved values of C
a
and L
a
of the associated apparatus are greater than C
i
+
C
cable
and L
i
+ L
cable
respectively for the intrinsically safe apparatus.
Wiring methods must be in accordance with the NEC, ANSI/NFPA 70,
Article 504 or the CEC CSA C22.1, Part 1, Appendix F. For additional
information refer to ANSI/ISA RP12.6.
Wiring methods must be in accordance with the NEC, ANSI/NFPA 70,
Article 501 or the CEC CSA C22.1, Part 1, Section 18.