Rockwell Automation 2080-LC10-12AWA_12QWB_12QBB_12DWD Micro810 12 Point 24V/12V DC Programmable Controllers User Manual
Page 13

Micro810 12 Point Programmable Controllers 13
Publication 2080-IN006B-EN-P - April 2014
North American
temp code
T5
Insulation
stripping length
7 mm (0.28 in.)
Isolation voltage
250V
(continuous),
Reinforced
Insulation Type,
I/O to Aux and
Network, Inputs
to Outputs.
Type tested for
60 s @
3250V DC, I/O to
Aux and Network,
Inputs to Outputs
250V (continuous), Reinforced
Insulation Type, I/O to Aux and
Network, Inputs to Outputs
Type tested for 60 s @ 720V DC,
Inputs to Aux and Network, 3250V DC
Outputs to Aux and Network, Inputs to
Outputs
50V (continuous),
Reinforced
Insulation Type,
I/O to Aux and
Network, Inputs
to Outputs
Type tested for
60 s @ 720V DC,
I/O to Aux and
Network, Inputs
to Outputs
AC input filter
setting
16 ms for all embedded inputs
Through the Connected Components Workbench software, go to the
Embedded I/O configuration window to re-configure the filter setting for each
input group.
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation
Wiring and Grounding Guidelines, publication
Non-isolated AC Inputs (2080-LC10-12AWA)
Attribute
Value
On-state voltage, nom
120/240 V AC
On-state voltage, min
79 V AC
On-state voltage, max
265 V AC
Off-state voltage, max
40 V AC
Operating frequency, nom
50/60 Hz
Input impedance
423.7 k
Ω
Operating frequency
47…63 Hz
General Specifications
Attribute
2080-LC10
12AWA
12QWB
12DWD
12QBB