FLEX Ex Power Supply 11
Publication
1797-5.12 - June 2010
Table 2 Environmental Specifications
Table 3 Certifications
Dimensions (HxWxD) approx. 140 x 174 x 174 mm
(5.51 x 6.9 x 6.9 in.)
Protections class
IP 66/NEMA 7B
Weight (approx.)
7.3 kg (16 lb)
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…70 °C (-4…158 °F)
Temperature, storage
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp
Heat):
5…95% noncondensing
Shock
Operating
Nonoperating
IEC60068-2-27 (Test Ea, Unpackaged shock):
15 g
15 g
Vibration
IEC60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Emissions
CISPR 11
Radiated, Class A
Conducted, Class B
Certifications (when
product is marked)
(1)
Value
UL, C-UL
Associated Apparatus, Class I, Zone 1, AEx ib IIC T4.
Providing intrinsically safe circuits for use in Class I, Zone 0,
Group IIC Hazardous Locations when installed per
Allen-Bradley Control Drawing No. 1797-6.5.6.
Associated Apparatus, Class I, Groups A, B, C and D;
Class II, Groups E, F and G; Class III Hazardous Locations.
Providing intrinsically safe circuits for use in Class I, Groups
A, B, C and D; Class II, Groups E, F and G; and Class III
Hazardous Locations when installed per Allen-Bradley Control
Drawing No. 1797-6.5.6.