Rockwell Automation 5000 Intrinsically Safe Version User Manual
Photoswitch, Division 1 installation wiring diagrams
Allen-Bradley Control Drawing #133-451 (Ver 08)
PHOTOSWITCH
®
Photoelectric Sensors Series 5000 Intrinsically Safe Version
Division 1 Installation Wiring Diagrams
10mA Max.
Load
Supply Return
Signal
Return
Power Supply
( + )
( -- )
Out
Gnd
Earth Ground
(less than 1 ohm)
In
Gnd
Barrier Bus
Gnd
AB #897H-S140
Out
AB #897H-S120
Gnd
In
Barrier Entity Parameters
Load Supply
Power Supply
Load
Supply Return
( + )
( + )
Out
Gnd
Earth Ground
(less than 1 ohm)
Gnd
In
In
Gnd
In
Gnd
Out
Load
Supply
( +5V DC)
Earth Ground
(less than 1 ohm)
Out
AB #897H-S120
Gnd
In
In
Gnd
Gnd
Out
Barrier Entity Parameters
Power Supply
42DRA--5500, 42DRU--5500
42DRP--5500, 42DRU--5700
42DTB--5500
NPN Open Collector Connections (Sinking)
(2 Barriers Required)
Class I, II, III, Division 1, Group C, D, E, F, G
Class I, II, III, Division 2, Group A, B, C, D, F, G
Zener Diode Barriers
Power Supply
& Load Circuits
Nonhazardous Location
Hazardous Location
Photoheads
Terminal Base
Vmax = 29.5V
Imax = 107mA
AB #897H-S120
Gnd
Load
TTL
Device
Supply Return
( + )
( + )
( + )
( -- )
PNP Open Collector Connections (Sourcing)
(3 Barriers Required)
Vmax = 29.5V
Imax = 107mA
Terminal Base
Photohead
Sink Wiring
Terminal Base
Photohead
Source Wiring
( + )
( 1 )
( -- )
( + )
( 2 )
( 3 )
( -- )
Barrier Bus
AB #897H-S120
Out
Barrier Entity Parameters
AB #897H-S120
Gnd
Barrier Bus
Gnd
AB #897H-S140
( -- )
Signal
Return
Class I, II, III, Division 1, Group A, B, C, D, E, F, G
Class I, II, III, Division 2, Group A, B, C, D, F, G
PNP Open Collector Connections (Sourcing)
(2 Barriers Required)
Vmax = 29.5V
Imax = 107mA
Terminal Base
Photohead
Source Wiring
( + )
( 2 )
( 3 )
( -- )
Notes:
Installation must be in accordance with the National Electrical Code
®
(NFPA 70, Article 504), ANSI/ISA--RP12.6, and the manufacturer’s instructions.
Barrier entity parameters: Voc 29.5V; Isc 107mA; Ca Ccable; La Lcable; recommended barriers are indicated on the above wiring diagram.
If the electrical parameters of the cable used are unknown, the following values may be used: Capacitance -- 60pF/ft.; IInductance -- 0.20 H/ft.
Barrier bus must be insulated from other grounded metal. Use DIN Rail Mounting Kit, Allen-Bradley #64--136.
Maximum nonhazardous area voltage must not exceed 250V.
Barriers are not required for Division 2 (29.5V DC max.). Division 2 applications must be installed in accordance with the National Electrical Code
®
.
An approved dust tight seal is required for Class II, III applications.
The output circuits of Zener Diode Barriers shall be in separate cables or separated from each other per NEC 504--30.
No revision to drawing without prior FMRC and UL approval.
Ci = 0 F
Li = 0 H
µ
µ
Ci = 0 F
Li = 0 H
µ
µ
Ci = 0 F
Li = 0 H
µ
µ
24V DC 8%
±
24V DC 8%
±
24V DC 8%
±
<
–
<
–
>
–
>
–
µ