beautypg.com

Rockwell Automation 2100 CENTERLINE MCC Installing Unit Load Ground Lugs User Manual

Page 2

background image

Publication 2100-IN064A-EN-P—September 2006

2

Copyright © 2006 Rockwell Automation, Inc. Printed in the U.S.A.

Supersedes Publication 2400-5.3 - October 1990

Figure 1 Assembling unit load ground lug kit

4. The ground lugs accept #14 to #4 AWG copper wire. Remove 1/2” of

insulation from the end of the wire. Insert the stripped end of the wire
into the lug. Torque to 45 lb-in (5 N-m).

A

B

C

D

E

2.0

1.0

Ground Bus

5/16” Diameter Holes

Parts List:

A. Ground lugs (2)

B. 1/4-20 x 1” hex head

screw (1)

C. 1/4” flat washer (1)

D. 1/4” lock washer (1)

E. 1/4-20 nut (1)

Front