Rockwell Automation 1798-APB FlexArmor PROFIBUS Adapter Module User Manual
Page 7
FlexArmor PROFIBUS Adapter Module 7
Publication 1798-IN011A-EN-P - March 2002
FlexArmor PROFIBUS Adapter Specifications (continued)
Freeze Mode
Supported
Sync Mode
Supported
Auto Baud Rate
Supported
Fail Safe Mode
Not Supported
Station Type
Slave
FMS Support
Not supported
Number of nodes
100 maximum - rotary switch type node address setting
(00-99)
Network Length/
Communication rate
9.6KBPS @ 1000m (3280ft)
19.2KBPS @ 1000m (3280ft)
45.45KBPS @ 1000m (3280ft)
93.75KBPS @ 1000m (3280ft)
187.5KBPS @ 1000m (3280ft)
500KBPS @ 400m (1312ft)
3MBPS @ 100m (328ft)
6MBPS @ 100m (328ft)
12MBPS @ 100m (328ft)
External DC Power (Input Power:)
Voltage (24V dc nom.)
Current
10-28.8V dc: 5% AC ripple
400 mA @ 24V dc
FlexBus (Output Power):
Voltage (5V dc nom.)
Current
4.75 - 5.2V dc; 5% AC ripple
640 mA @ 5.2V dc
Indicators
1 red/green module status
1 red/green network status
Wiring
Refer to publication 1770-4.1 Programmable Controller
Wiring and Grounding Guidelines
Isolation
Type test 1250Vac rms for 60 seconds between field
power and PROFIBUS (I/O to logic)
Dimensions (H x D x W)
118 mm X 50 mm X 40 mm
4.63 in. X 1.95 in. X 1.58 in.
Operational Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 55°C (32 to 131°F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating
Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry
Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating
Thermal Shock):
–25 to 85°C (–13 to 185°F)
Shock
IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g
Emissions
CISPR 11:
Group 1, Class A