Replace battery in panelview component terminals, 400 and 600 terminals – Rockwell Automation 2711P-RY2032 Battery Replacement Installation Instructions User Manual
Page 5
Battery Replacement 5
Rockwell Automation Rockwell Automation Publication 2711P-IN009F-EN-P - July 2014
10. Tighten the captive screws that secure the logic module to the display module and torque
to 0.58…0.79 N•m (5…7 lb•in).
11. Reattach the communication module, if necessary, and tighten the screws to a torque of
0.58…0.79 N•m (5…7 lb•in).
Replace Battery in PanelView Component Terminals
The PanelView Component C400, C600, and C1000 terminals, catalog numbers 2711C-T4T,
2711C-T6
x, and 2711C-T10C, contain a lithium battery on the back of the terminal. No
special tools are required to remove the battery cover and replace the battery.
Follow these steps to replace the battery in the PanelView Component terminals.
1. Disconnect power from the terminal.
2. Remove or unlatch the battery cover on the back of the terminal.
3. Remove the battery.
4. Insert the new battery with the positive polarity (+) facing up.
Replace Battery in PanelView Plus 6 and PanelView Plus 6 Compact
Terminals
400 and 600 Terminals
You can replace the battery with the terminal mounted in the panel. No special tools are required
to remove the battery.
Follow these steps to replace the battery in a 400 or 600 terminal.
1. Disconnect power from the terminal.
Battery
Cover
Battery
C600 /C1000